  HYBRID POWER RELAYS - RHP
 
 
  • 20 A in a case only 17.5 mm wide
  • Service life > 5 million operations at full load
  • Silent operation
  • Function contactor - impulse relay - day/night contactor
  • Clips onto a 35 mm DIN rail
  • UL/@UL (listed) approval pending
  • NF-USE label pending
  • "CE" / Low Voltage Directive conformity
Operating principles
Contactor

The contactor output is closed when the control voltage is present at the control input terminals.
The contactor output is open when there is no voltage at the control input terminals
The LED is lit when the output is active

Impulse relay

The impulse relay output changes state on each impulse at the control input terminals and remains in that state between each impulse. The output changes state on the rising edge of the control state change.The pushbutton on the front can be used to select an operating mode:

  • Automatic (LED lit): Impulse relay function (Auto)
  • Forced operation (LED flashing) : output closed (ON)
  • Stop (LED not lit) : output open (OFF)
 
Day/night contactor

The contactor output is closed when the control voltage is present at the control input terminals.
The contactor output is open when there is no voltage at the control input terminals
The pushbutton on the front can be used to select an operating mode:

  • Automatic (LED lit) : Day/night contactor function (Auto)
  • Forced operation (LED flashing) : output closed (ON)
    When the control changes state, the day/night contactor reverts to automatic mode
  • Stop (LED not lit) : output open (OF)
Conformity with Standards
IEC/EN 60947-4-3 (industrial environment)
IEC/EN 60669-2-1 (domestic environment)
IEC/EN 60601-1 (medical environment)
IEC/EN 60947-7-1 (connection for industrial env.)
IEC/EN 60998-2-1 (connection for domestic env.)

Insulation coordination:
Installation category: 3
Degree of pollution: 3
According to IEC 60664-1 : 4 KV/3

Breakdown voltage according to IEC/EN60669-2-1 : 2 KV/1 Min / 1 mA / 50 Hz
Insulation resistance according to IEC/EN60669-2-1 : 5 M/500VDC/ 1 Min
Vibrations according to IEC/EN60068-2-6 : frequencies : 10 to 55Hz amplitude: 0.35 mm

Part numbers (and voltages)
 
Contractor Control ~
84 138 001
Contractor Control
84 138 000
Impulse relay control ~
84 138 101
Day/night contactor control
84 138 201
 
Input characteristics
 
Voltage
90...260 V a
0...32 V c
Frequency
50 / 60 Hz
 
Thresh - OFF control
0 to 46 V~
0 to 1 V
olds     - ON control
76 to 260 V ~
4 to 32 V
Minimum duration of the control
50 ms
50 ms
Output Characteristics
 
Voltage 90...260 V~
Max. current 20 A in AC1 / AC51 / AC7a
Overload current 20 A AC-51 : 1,25 x le - 60s : 50 - 30 (IEC 60947-4-3)
Min. Current 100 mA in AC1 / Ac51 / AC7a
Frequency 50 / 60 Hz
Contact > 5 000 000
Leakage current < 5 mA
Acoustic in steady state
noise on switching
< 35 dB at 1 m
< 50 dB at 0.5 m
Terminal block clamping capacity:
2 x 1.5 mm2 with ferrule
2 x 2.5 mm2 without ferrule
1 x 4 mm2 without ferrule
Terminal tightening torque 1 Nm max. M3 screw (IEC60947-1)
Operating Temperature -5°C to + 55°C
Storage temperature -40°C to + 85°C
Relative humidity 90 to 95% without condensation
Casing material Self-extinguishing
Degree of protection
(according to IEC 60529)
IP 50 casing
IP 20 terminal block
Weight (g) 70 approx.
 
Connection
 
Dimensions