A in a case only 17.5 mm wide
- Service
life > 5 million operations at full load
- Silent
operation
- Function
contactor - impulse relay - day/night contactor
- Clips
onto a 35 mm DIN rail
- UL/@UL
(listed) approval pending
- NF-USE
label pending
- "CE"
/ Low Voltage Directive conformity
|
|
| Operating
principles |
|
| Contactor |
|
The contactor
output is closed when the control voltage is present at the
control input terminals.
The contactor output is open when there is no voltage at the
control input terminals
The LED is lit when the output is active
|
|
| Impulse
relay |
|
The impulse
relay output changes state on each impulse at the control
input terminals and remains in that state between each impulse.
The output changes state on the rising edge of the control
state change.The pushbutton on the front can be used to select
an operating mode:
- Automatic
(LED lit): Impulse relay function (Auto)
- Forced
operation (LED flashing) : output closed (ON)
- Stop
(LED not lit) : output open (OFF)
|
|
| Day/night
contactor |
|
The contactor
output is closed when the control voltage is present at the
control input terminals.
The contactor output is open when there is no voltage at the
control input terminals
The pushbutton on the front can be used to select an operating
mode:
- Automatic
(LED lit) : Day/night contactor function (Auto)
- Forced
operation (LED flashing) : output closed (ON)
When the control changes state, the day/night contactor
reverts to automatic mode
- Stop
(LED not lit) : output open (OF)
|
| Conformity
with Standards |
IEC/EN
60947-4-3 (industrial environment)
IEC/EN 60669-2-1 (domestic environment)
IEC/EN 60601-1 (medical environment)
IEC/EN 60947-7-1 (connection for industrial env.)
IEC/EN 60998-2-1 (connection for domestic env.) |
|
|
Insulation
coordination:
Installation category: 3
Degree of pollution: 3
According to IEC 60664-1 : 4 KV/3
Breakdown
voltage according to IEC/EN60669-2-1 : 2 KV/1 Min / 1 mA /
50 Hz
Insulation resistance according to IEC/EN60669-2-1 : 5 M /500VDC/
1 Min
Vibrations according to IEC/EN60068-2-6 : frequencies : 10
to 55Hz amplitude: 0.35 mm
|
|
| Part
numbers (and voltages) |
| |
|
Contractor
Control ~
|
84
138 001
|
Contractor
Control 
|
84
138 000
|
|
Impulse
relay control ~
|
84
138 101
|
Day/night
contactor control 
|
84
138 201
|
|
| |
| Input
characteristics |
| |
| Voltage |
90...260
V a
|
0...32
V c
|
| Frequency |
50
/ 60 Hz
|
|
| Thresh
- OFF control |
0
to 46 V~
|
0
to 1 V 
|
| olds -
ON control |
76
to 260 V ~
|
4
to 32 V
|
| Minimum
duration of the control |
50
ms
|
50
ms
|
|
|
| Output
Characteristics |
| |
| Voltage |
90...260
V~ |
| Max.
current |
20
A in AC1 / AC51 / AC7a |
| Overload
current 20 A |
AC-51
: 1,25 x le - 60s : 50 - 30 (IEC 60947-4-3) |
| Min.
Current |
100
mA in AC1 / Ac51 / AC7a |
| Frequency |
50
/ 60 Hz |
| Contact |
>
5 000 000 |
| Leakage
current |
<
5 mA |
| Acoustic |
in
steady state |
| noise |
on
switching |
|
| <
35 dB at 1 m |
| <
50 dB at 0.5 m |
|
| Terminal
block clamping capacity: |
| 2
x 1.5 mm2 with ferrule |
| 2
x 2.5 mm2 without ferrule |
| 1
x 4 mm2 without ferrule |
|
| Terminal
tightening torque |
1
Nm max. M3 screw (IEC60947-1) |
| Operating
Temperature |
-5°C
to + 55°C |
| Storage
temperature |
-40°C
to + 85°C |
| Relative
humidity |
90
to 95% without condensation |
| Casing
material |
Self-extinguishing |
Degree
of protection
(according to IEC 60529) |
| IP
50 casing |
| IP
20 terminal block |
|
| Weight
(g) |
70
approx. |
|
| |
| Connection |
 |
| |
|